Gas Solenoid Valves and Automatic Gas Shut-Off Valves

A gas solenoid valve is the part of a gas detection system that actually stops the gas. It sits on the supply pipe, stays open while its coil is powered, and closes the moment the detection panel, an emergency stop button or the fire alarm cuts that power. We supply, fit, commission and service gas solenoid valves from Madas, Coster and Bürkert for natural gas and LPG across Ireland.

Madas automatic gas solenoid valve for natural gas and LPG

How an automatic gas shut-off valve works

The valves we fit for gas safety are normally closed. That means they need power to stay open. When a detector reaches its alarm level, the panel removes power from the valve coil and the valve springs shut, cutting off the gas supply to the room. The same happens if the power fails, so the system fails safe rather than leaving gas flowing.

Because the valve closes on loss of power, it can be wired to more than one trigger: the gas detection panel, an emergency gas shut-off button by the door, the fire alarm, or the extract fan interlock in a commercial kitchen. Once it has closed, it stays closed until someone checks the area and resets it.

The gas valves we supply

We choose the valve to match the gas, the pipe size, the supply pressure and the panel it will be wired to. These are the ranges we fit most often.

ValveBest forKey points
Madas automatic valvesNatural gas and LPG shut-off on most commercial sitesNormally closed, DN8 to DN300, versions from 0.2 to 6 bar, fast or slow opening, IP65 or ATEX (Zones 2 and 22, or Zones 1 and 2), built to EN 161
Coster GCA 865 / 880Larger flanged gas mains, such as boiler housesNormally closed, DN65 and DN80 flanged PN16, 230V coil (24V versions available), up to 360 mbar, opens and closes in under one second, Class A to EN 161
Bürkert Type 6281Neutral gases and liquids at higher pressureServo-assisted, normally closed, 0.2 to 16 bar, DN10 to DN50, brass or stainless steel, IP65, ATEX and IECEx versions

Which valve does your site need?

For shutting off a fuel gas supply on a gas alarm, we normally fit an EN 161 gas valve such as Madas or Coster. EN 161 is the European standard for automatic shut-off valves for gas burners and appliances, and it sets construction and performance requirements for them, including how fast they close. Bürkert servo-assisted valves are general purpose valves for neutral media at higher pressures, and we fit them where that is what the process needs.

Four things decide the choice: the gas, the pipe size, the supply pressure at the valve, and whether the valve sits in a hazardous area. If it does, an ATEX version certified for that zone is required. Our ATEX gas detectors page covers equipment for hazardous areas, and our guide to ATEX zones explains how zones are set.

Where gas shut-off valves are fitted

Any room where a gas leak could build up is a candidate. In a boiler room, the valve sits on the incoming gas line and closes when the methane or carbon monoxide detectors go into alarm. In a commercial kitchen or a school science room, the valve is part of a gas interlock system that only lets gas flow while the extract ventilation is running. In a laboratory, a valve on the bench gas supply can be closed from the detection panel or a stop button by the door.

The valve is fitted on the gas pipework, so that part of the work is done by a Registered Gas Installer. We supply the valve, wire it to the gas detection panel, commission the system and test that the valve closes on alarm.

Testing and servicing gas valves

A valve that has not moved in years may not close when it is needed. As part of a maintenance contract or a service visit, we put each detector into alarm with certified test gas and confirm that the valve closes, the alarms sound and the system resets correctly. We record the results for your safety file. We also service and replace valves on systems we did not install.

Common questions

What is a normally closed gas solenoid valve?

It is a valve that is closed whenever its coil has no power. Power holds it open. When a gas detection panel removes that power on alarm, or the mains fails, the valve closes and stops the gas. That is why normally closed valves are used for gas safety shut-off.

Can a gas solenoid valve be linked to the fire alarm?

Yes. Because the valve closes when power is removed, it can be wired so that a fire alarm signal, an emergency stop button or the gas detection panel can each close it.

Do you supply ATEX gas valves?

Yes. Madas valves are available in ATEX versions for Zones 2 and 22, or Zones 1 and 2, and Bürkert Type 6281 valves come in ATEX and IECEx versions. The version is chosen to match the zone the valve will sit in.

Who can fit a gas shut-off valve in Ireland?

The work on the gas pipework must be done by a Registered Gas Installer. We supply the valve, connect it to the gas detection system, commission it and test it.

How often should a gas shut-off valve be tested?

It should be tested whenever the gas detection system is serviced, by putting a detector into alarm and checking that the valve closes. Your maintenance schedule and the manufacturer’s instructions set the interval.

Need a gas shut-off valve?

Tell us the gas, the pipe size and the supply pressure, and we will recommend the right valve and link it to your gas detection. Call 01 289 7720 or email info@vistec.ie.